P/N: ETI0015-2203AD
PersonalSource™ Rugged COTS
1000 VA Rackmount UPS
with Extended Battery Time
True On-Line Design |
RS232 Communications |
30 Minutes Battery Time | Site Wiring Fault indicator |
Input Power Factor Correction | Green Mode Operation |
Microprocessor Control & Communications | Built-in Surge Protection |
Compact size, lightweight | Compatible with generators |
Wide input voltage window | Optional internal SNMP/HTTP |
High Efficiency | Optional Frequency Conversion |
Over crest ratio indicator |
PersonalSource Rugged COTS Rackmount 1000 VA Front View
PersonalSource Rugged COTS Rackmount 1000 VA Rear View
True On-line Design
A recent Bell Laboratories study indicates that blackouts accountfor less than 5% of power disturbances. The other 95% consist of surges, noise,sags and brownouts. Equipment connected to utility power experiences an averageof 128 such events each month. These events can disrupt proper operation ofsensitive computer based equipment, decreasing productivity and createsunnecessary production, service and data recovery costs.
A True On-line UPS is the only design that can provide the maximumprotection against major power problems. This is accomplished through convertingthe incoming AC utility voltage to a DC voltage. From this DC voltage, an ACvoltage is then completely regenerated by the UPS, providing a clean,well-regulated source to your equipment, thereby eliminating power relatedproblems. This solidstate generator sets the True Regenerative On-Line UPS apartfrom all other Line-interactive and Off-line designs, which leave your sensitiveequipment connected directly to the dirty utility power 99+% of the time. Ifyour equipment is operating in a “Mission Critical” application, then youneed a True On-line UPS and the PersonalSource is the best choice in TrueOn-line UPS technology.
Input Power Factor Correction
All PersonalSource Seriesmodels include state of the art Input PowerFactor Correction. This greatly reduces the amount of current demanded fromyour building wiring system, yielding an efficient, “building friendly” UPS.
Microprocessor Control
The PersonalSourceUPS incorporates advanced microprocessor technology. This technology makespossible a high level of internal UPS control as well as system information,data logging, self-diagnostics, SNMP and enhanced computer communication throughany RS-232 port.
SNMP/HTTP RemoteManagement Support
An optional SNMP/HTTPAgent board is available for direct installation into all PersonalSource models.The SNMP/HTTP Agent provides for direct connection of the UPS to any 10BaseT Ethernet LAN.
Overall, the PersonalSource Series is uniquely qualified for critical systems combining advanced modular design features with highlyreliable construction.
PART NUMBER: |
ETI0015-2203AD |
||
INPUT |
Nominal Voltage: |
120 V AC |
|
Voltage Range: |
87-140V AC |
||
Current (max): |
4.5A |
||
Frequency: |
50/60Hz ±5% |
||
Efficiency: |
|
||
Power Factor: |
|
||
OUTPUT |
VA Rating: |
1000 VA |
|
Power: |
700W |
||
Voltage: |
120 VAC std |
||
Frequency: |
50 or 60Hz (auto tracking) |
||
Voltage Regulation: |
±2% |
||
Frequency Stability: |
±0.3% (Battery mode) |
||
Step Load Change: |
±7% for 100% load variation |
||
Harmonic Distortion: |
Linear Load <3% |
||
Overload: |
105% load for 50 seconds |
||
Crest Ratio: |
3:1 |
||
BATTERY2 |
DC Voltage: |
36 VDC |
|
Type: |
Maintenance Free, Valve Regulated, Sealed Lead Acid, Flame Retardant, Absorbed Electrolyte |
||
Backup time |
Full Load |
30 minutes typical |
|
Recharge Time: |
8 Hours to 90% |
||
TRANSFER TIME |
Line Fails/Recovers: |
Zero time – true online, no transfer for brownout or blackout |
|
UPS to Bypass or Reverse: |
<4 ms for bypass transfers |
||
After Overload: |
Auto Transfer to UPS |
||
Audible Noise |
@ 1 Meter |
<50dBA |
|
Indicators |
LEDs: |
Line, Inverter, Battery Reserve, Load, Bypass, Alarm, Crest, Battery & Load Capacity Level |
|
Audible Alarms |
|
DC Mode, Low Battery, Over/Under Voltage, Over/Under Frequency, High Temperature, Over Load, Alarm. |
|
Interface |
Computer: |
UPS industry style RS-232 |
|
Environment |
Temperature: |
0°C - 40°C (32°F – 104°F) |
|
Humidity: |
10% - 95% Non-condensing |
||
Mechanical |
Input Line Cord: |
6 Foot Cord with NEMA 5-15P Plug |
|
Output Receptacles: |
(6) NEMA 5-15R with cable bales |
||
Weight: |
65 lbs (30 kg) |
||
Dimensions: |
5.25 (3U) x 23.5 x 19.0 |
||
Approvals |
Agency: |
UL, CUL, FCC Class A (CE on European models only) |