Part Number:
ETI0001-2250AB
Ultra Rugged Mil Spec® 2000 VA UPS
with Hotswap Drawout Battery Module
Backward Compatible w/ US Navy / Raytheon Q70 (AN/UYQ-70) Systems
Backward Compatible w/ all ATWCS, TTWCS,Tomahawk, TAC-4 and TAC-JW Systems
Military Power® Mil Spec Configuration, 2000 VA Isolated UPS
Rugged Rack Mount with Global Isolated Input
Input PFC, Battleshort Override and Elapsed Time Indicator
Plus Front Access Hot Swappable Battery Module
Direct Replacement for:
ETI P/N:
ETI0001-2250
ETI P/N:
ETI0001-1237, ETI Model:
ETI0001-S1R-KII/2.0
Raytheon P/Ns: G788631-1, G7866416-1 and G788631-1
Lockheed Martin P/Ns: 20534121G01 and 79C0768-00
US Navy P/N:72206, TAC-4 P/N: S5257-00001
NSN: 6130-01-462-8656 or 6130-01-470-8743 or6130-01-470-1368 or 6130-01-530-3056 or 6130-01-523-4761
Milpower Source P/N:M-120BA-1A
AP Labs P/N: 12928
Naval Air Systems Command P/N: 3686AS2946-1
P/N:
ETI0001-2250AB Rugged Mil Spec UPS Standard Front Panel Layout
with Hotswap Drawout Battery Module
P/N:
ETI0001-2250AB Rugged Mil Spec UPS Standard Rear Panel Layout
The field proven Military Power® UPS line is ideally suited for military,industrial, computer and telecommunications applications requiring high reliability, rugged construction, compact size and light weight design.These units are equally suited for use in shipboard, airborne, vehicular, fielddeployed or fixed locations with controlled or uncontrolled environments.The
ETI0001-2250AB was specifically designed to mountin the TAC-4 racks and interface with either the TAC-4 PDU or any of numerous ETIPDUs.
The heavy-duty chassis occupies only 5.25" (3U) of rack space while delivering up to2000 VA of clean, uninterruptible power. The rounded metal corners and rugged handles, aidin safe handling. Internally, all major components are well secured and electricallyinsulated to prevent damage due to shock and vibration. The optional heavy-duty rack slides provideeasy installation and removal of the unit with full extension. Rear shockisolation/alignment bushings off load the slides when the unit is fully engaged.
The internal shielded input transformerprovides galvanic isolation with provisions for both domestic(115 VAC, CONUS) and international (230 VAC, OCONUS) input voltages. Theinput voltage selection allows inputting either 115 VAC or 230 VACwithout having to open the UPS enclosure.Special EMI/RFI filters and inputpower factor correction minimize both input current and harmonics. Theunit also operates as a frequency converter, taking 46-70 hertz input andconverting it to clean, uninterruptible 60 hertz power. Optionally, 46-440hertz input as well either 50or 400 hertz outputs are available.
The LED arrays keep the operatorinformed as to the unit's status including load and battery levels. The Elapsed Time Indicator records the number of operational hours for records and scheduling preventative maintenance of attached equipment. The front panel also provides easy access to both the AC Input and Battery Input fuses. Coupled with the adjacent spare fuses, MTTR is reduced to less than 15 minutes.
The internal intelligent thermalsensors provide two stage monitoring of unit temperatures,with both local andremote Battleshort override capability of thermal shutdown. Battleshort can beengaged via the front panel control, via a remote contact input or via asoftware command. When in Battleshort, an audible alarm is sounded and anindicator is lit. Thehigh intensity audible alarm can be heard in high noise environments andincludes an audible enable/disable switch.
All controls and protective devices are brought to the front and rear panels with critical switches or circuit breakers having finger guards. Further, all front panel devices are recessed to prevent damage or accidental operation. The input circuit breaker and the galvanic isolation transformer all provide a double pole isolated source for all installations including shipboard systems or overseas locations where phase references and grounding are not consistent.
The rear panel provides lockingconnectors for the input and output power with various optional configurationsavailable. This reverse air flow version draws air through the front and exhausts out the rearvent into the rack. A removable and washable intake air filter and high capacitystainless steel ballbearing fan provide added protection in both controlled and hostile environments. Clips on the rear panel hold additional spare fuses for ready access.
The
ETI0001-2250AB has the added benefit ofhaving a field replaceable battery via front drawoutbattery module. The battery is a true hot-swappable module and does notrequire going to bypass like competing units. Even with this batterymodule removed, this UPS can continue to operate as an electronic powerconditioner and frequency converter, providing clean, well regulated, sinusoidalpower to the load.The batteries are maintenance free with immobilized electrolyte and areconstructed of flame retardant materials for added safety. For more information, see the BatteryTechnology section.
The twostatus D shell connectors provide both a contact and serial interface withoptional computer software providing loss of AC and low battery status as well as remote shut downcapability. See the Power Distribution Units section for a listing ofstand alone PDUs. See the N5 Series
ETI0001-1437 for aversion of this UPS with an integrated PDU and remote control.
For a side by side comparison of
ETI0001-2250 vs.
ETI0001-2250AB, click here.
Overall, the Military Power line is uniquely qualified for critical shipboard, vehicle,airborne or land based systems combining advanced modular design features with highlyreliable construction.
AC OUTPUT | |
Output voltage: | 120 VAC true sinewave standard, others optional |
Output rating: UPS | 2000 VA standard in 3U chassis 0.65-0.75 pf std, optional configurations to 24,000 VA |
Non-linear load capacity: | Up to 100% non-linear load capability w/o derating |
Output voltage regulation: UPS | ± 3.0% static regulation of nominal ± 4.0% dynamic (0 to 50% load step) |
Overload surge capacity: | 110% for 10 minutes; 125% for 30 seconds |
Harmonic distortion: | Less than 5.0% into 100% non-linear load |
Output frequency: UPS | 60 Hz ± 1.0% independent of input frequency 50, 400 or 1000 Hz output available as an option |
Operational status | AC Input status, UPS operational, UPS alarm, Battery level, Low battery, Load level, Overload, Warm temperature, Hot temperature, On Battery and Battleshort LEDs, Elapsed time hour meter Alarm contacts for Loss of AC and Low Battery +90 dB audible alarm with audible on/off switch Asynchronous serial COM port |
AC INPUT | |
Input voltage selection: | Nominal 115 VAC or 230 VAC via selection switch (S6) |
Input voltage tolerance: UPS | 85-135 VAC or 170-270 @ full load without using battery, to 70 VAC @ 75% load |
Input frequency: | From 46 Hz to 70 Hz standard, optional to 440 Hz |
Input power factor: | Better than 99% typically |
Input/output isolation: | 2000 VA, 120 dB common mode, <1.0 mA leakage |
Input transient suppression: | Complies with IEEE 587 and UL 1449 |
Input control/protection: | Guarded 2 pole 100 G shock rated circuit breaker (CB1) plus UPS input fuse (F2), spare fuses on front and rear Optional cold start switch available to turn on w/o AC present |
Input control/protection: | Guarded 2 pole switch (S1) w/fuse (F2) |
Input power connection: | MS 3102A-22-2P, 3 pin, locking |
INTERNAL BATTERY | |
Battery type: | Maintenance free immobilized electrolyte, Flame retardant materials (Oxygen Index 28+) |
Battery life: | Rated for continuous service life of 5 years |
DC protection: | Front panel mounted fuse standard, breaker optional |
Battery time: | 15+ minutes @ 100% load, 30+ minutes @ 50% |
Battery recharge: | Recharged to nominal in <8 hours |
Internal battery replacement: | Hot swap drawout/plug-in module from front of unit <3 minutes to change battery modules |
Battery expansion: | Up to 24 hours w/ optional Battery Expansion Modules |
DISTRIBUTION PANEL | |
Output circuits: | One output standard, optional configurations |
Output control: | Guarded 3 pole switch (S5) |
Output receptacles: | MS 3102A-24-10S, 7 pin locking, other options |
MECHANICAL | |
Dimensions ( H x D x W ): | 5.25 (3U) x 28.0 x 19.0 in (133 x 711 x 483 mm) |
Rack Slide Mount Patterns: | Actron/Jonathan slide pattern, others optional |
Rack rear alignment pins: | (2) shock isolation/alignment pin/socket sets |
Alternate Mounting Options: | Table, Wall, Floor, Portable, Horizontal/Vertical |
Unit weight: UPS and Battery UPS only Battery Module only |
155 lb. (70 kg) with lift handles front and rear 95 lb. (43 kg) with lift handles front and rear 60 lb. (27 kg) with lift handle in front |
Audible noise: | Less than 47 dB @ 5.0 ft., ANSI "A" scale |
Cooling type: | High capacity, negative pressure, forced air |
Cooling air direction: | Front intake, exhaust to rear, others optional |
Air intake filter: | Washable metal filter media, others optional |
ENVIRONMENTAL | |
Storage temperature: | -40° to 158° F ambient (-40° to 70° C) with fully charged batteries |
Operating temperature: | -4° to 131° F ambient ( -20° to 55° C), lower/ higher optional |
Operating humidity: | 0 to 95% relative humidity (non-condensing) |
Storage elevation: | Up to 40,000 ft (12,192 m) |
Operating elevation: | Up to 15,000 ft (4,572 m), higher optional |
STANDARDS | |
United States: | Meets UL-1778 standard for UPS equipment, MIL STDs 167-1, 454, 810, 901D Grade A, 1399-300A & 2000 |
Canada: | CSA C22.2 No. 107 UPS safety requirements |
EMI Protection: | EMI/RFI FCC Part 15, Class A; EN55022; MIL STD 461 |
OPTIONAL ACCESSORIES | |
Autoranging International Input, Emergency Power Off, Elapsed Time Meter, Cold Start, Alternate I/O Configurations, Dual Source Input, Battery Expansion, Batteryless Operation, Battery Charger/Conditioner, Power Distribution Units, Software Interface, 10BaseT Ethernet SNMP/HTTP port, Transport Cases |