P/N: ETI0001-2241 2.0 kVA Rugged Rackmount or Fixed Mount MilSpec UPS

Part Number:
ETI0001-2241
Rugged Rackmount or Fixed Mount
Mil Spec® 2000 VA UPS
and Frequency Converter


Supports Ground Base Radar Systems
2.0 kVA Mil Spec UPS and Frequency Converter
Rugged Rack or Fixed Mount Unit 
w/ Reduced Depth and Light Weight Design

ETI0001-2241 Rugged MilSpec UPS and Frequency Converter

ETI0001-2241 Rugged Mil Spec UPS and Frequency Converter
Standard Front Panel Layout

ETI0001-2241 Rugged MilSpec UPS and Frequency Converter

ETI0001-2241 Rugged Mil Spec UPS and Frequency Converter
Standard Rear Panel Layout

The field proven Military Power® UPS line is ideally suited for military,industrial, computer and telecommunications applications requiring high reliability, ruggedconstruction, compact size and light weight design. These units are equallysuited for use in shipboard, airborne, vehicular, field deployed or fixedlocations with controlled or uncontrolled environments. The
ETI0001-2241 is being used by Ground Base Radar Systems becauseof their stringent performance and reliability requirements. 

The heavy-duty chassis,occupying only 5.25" (3U) of rack space and 18.5" depth, has rounded metal cornersand rugged handles front and rear, aiding in safe handling. The chassisis constructed of brushed aluminum to minimize overall weight. Internally, all majorcomponents are well secured and electrically insulated to prevent damage due to shock andvibration. 

The internal shieldedinput transformer provides galvanic isolation with provisions for domestic (115 VAC, CONUS) and optionally for international (230 VAC, OCONUS) inputvoltages. Special EMI/RFI filters and inputpower factor correction minimize both input current and harmonics. The unit also operatesas a frequency converter, taking 46-70 hertz input and converting it to clean,uninterruptible 60 hertz power. The input switch and the galvanic isolationtransformer all provide a double pole isolated source for all installations including shipboardsystems or overseas locations where phase references and grounding are notconsistent. 

The LED arrays keep theoperator informed as to the unit's status including load and battery levels. Thehigh intensity audible alarm can be heard in high noise environments. All controlsand protective devices are brought to the front and rear panels with critical switches having fingerguards. Further, all front panel devices are recessed to prevent damage or accidentaloperation. Variousoptional power distribution controls are available which mount on the front panel orremotely. 

The rear panel provides locking connectors for the input and outputpower. Multipleinput and output power panel options are available. Removable and washable air filters and a high capacitystainless steel ball bearing fans provideadded protection in both controlled and hostile environments. The exhaust air is diverted out the frontvent, with alternateair flow directions optional.The batteries are maintenance free with immobilized electrolyte and areconstructed of flame retardant materials. For more information, see the BatteryTechnology section. The Status connector provides aninterface with optional computer software providing loss of AC and low battery status as well asremote shut down capability. 

See the Power Distribution Units section for alisting of stand alone PDUs. See the N5 Series
ETI0001-1445
for a version of this UPS with an integrated PDU and remote control.

Overall, the MilitaryPower line is uniquely qualified for criticalshipboard, vehicle, airborne or land based systems combining advanced modular designfeatures with highly reliable construction.

Technical Specifications:
P/N:
ETI0001-2241

AC OUTPUT
Output voltage: UPS 120 VAC true sinewave standard, up to 600 VAC optional
Output rating: UPS 2000 VA standard in 4U x 18.5" deep
0.65-0.75 pf standard, optional configurations to 24,000 VA
Non-linear load capacity: UPS Up to 100% non-linear load capability w/o derating
Output voltage regulation: UPS ± 3.0% static regulation of nominal
± 4.0% dynamic (0 to 50% load step)
Overload surge capacity: UPS 110% for 10 minutes; 125% for 30 seconds
Harmonic distortion: UPS Less than 5.0% into 100% non-linear load
Output frequency: UPS 60 Hz ± 1.0% independent of input frequency
50, 400 or 1000 Hz output available as an option
Operational status Status, load and battery LEDs, w/contacts
Adjustable level,+90 dB audible alarm w/on/off
AC INPUT
Input voltage selection: Nominal 115 VAC, optional autoranging input of 85-270 VAC
Input voltage tolerance: UPS 85-135 VAC @ full load without using battery, to 70 VAC @ 75% load
Input frequency: From 46 Hz to 70 Hz standard, optional up to 440 Hz
Input power factor: Better than 99% typically
Input/output isolation: 2000 VA, up to 120 dB common mode, <1.5 mA leakage
Input transient suppression: Complies with IEEE 587 and UL 1449
Input control/protection: Guarded 2 pole switch w/ fuse, optional breaker
Optional cold start to turn on w/o AC present
Input power connection: MS 3102A-22-2P, 3 pin, threaded locking
INTERNAL BATTERY
Internal battery type: Maintenance free immobilized electrolyte,
Flame retardant materials (Oxygen Index 28+)
Internal battery life: Rated for continuous service life of 5 years
Internal DC protection: Front panel mounted fuse standard, breaker optional
Internal battery time: 1+ minutes @ 100% load, 4+ minutes @ 50%
Internal battery recharge: Recharged to nominal in <8 hours
DISTRIBUTION PANEL
Output circuits: Six outputs standard, optional configurations
Output control: Optional remote control panel w/rocker switches
Output receptacles: NEMA 5-15R standard, other options
MECHANICAL
Dimensions ( H x D x W ): 5.25 (3U) x 18.5 x 19.0 in (133 x 470 x 483 mm)
Rack Slide Mount Patterns: Jonathan, General Devices patterns, others optional
Alternate Mounting Options: Table, Wall, Floor, Portable, Horizontal/Vertical
Unit weight: UPS 86 lb. (39 kg) UPS with lift handles front and rear
Audible noise: Less than 47 dB @ 5.0 ft., ANSI "A" scale
Cooling type: High capacity, positive pressure, forced air
Cooling air direction: Rear intake, exhaust to front, others optional
Air intake filter: Washable metal filter media, others optional
ENVIRONMENTAL
Storage temperature: -40° to 158° F ambient (-40° to 70° C) with fully charged batteries
Operating temperature: -4° to 131° F ambient ( -20° to 55° C), lower/ higher optional
Operating humidity: 0 to 95% relative humidity (non-condensing)
Storage elevation: Up to 40,000 ft (12,192 m)
Operating elevation: Up to 15,000 ft (4,572 m), higher optional
STANDARDS
United States: Meets UL-1778 standard for UPS equipment,
MIL STDs 167-1, 454, 810, 901D Grade A, 1399-300A & 2000
Canada: CSA C22.2 No. 107 UPS safety requirements
EMI Protection: EMI/RFI FCC Part 15, Class A, MIL STD 461 standard
OPTIONAL ACCESSORIES
Autoranging International Input, Cold Start, Emergency Power Off, Elapsed Time Meter, Alternate I/O Configurations, Dual Source Input, Battery Expansion, Batteryless Operation, Battery Charger/Conditioner, Power Distribution Units, Software Interface,  Asynchronous serial COM port, 10BaseT Ethernet SNMP/HTTP port, Transport Cases, Slides and Mounting Kits

This page was last modified on:April 10, 2012

Request Product Information
*(denotes required field)
Contact ETI by mail at:
Energy Technologies, Inc.
219 Park Avenue East
Mansfield, OH 44902-1845
USA

Contact ETI by phone or fax:
Voice: 419-522-4444
FAX: 419-522-4466