Part Number:
ETI0001-1437
Ultra Rugged Mil Spec® 2000 VA
Integrated Rackmount UPS and Intelligent
Power Distribution Unit Combination
TAC-4, TAC-JW, Tomahawk and Hewlett Packard StandardProduct Standard S1 Configuration, Military Power® Isolated UPS
Mil Spec 2000 VA Rugged Rack Mount,w/ PFC and Integrated 6 Circuit,
2 Pole, Intelligent, Solidstate Power Distribution Unit
P/N:
ETI0001-1437 Rugged Mil Spec UPS Standard Front Panel Layout
P/N:
ETI0001-1437 Rugged Mil Spec UPS Standard Rear Panel Layout
Optional P/N:
ETI0001-0876 UPS and PDU Remote Control Panel in 1U
The field proven Military Power® UPS line is ideally suited for military,industrial, computer and telecommunications applications requiring high reliability, rugged construction, compact size and light weight design.These units are equally suited for use in shipboard, airborne, vehicular, fielddeployed or fixed locations with controlled or uncontrolled environments.The "
ETI0001-1437" was specifically designed to mountin the TAC-4 racks BUT does not require a separate PDU as in TAC-4.The PDU functions are already integrated into the UPS module. This saves rack space, cabling andexpense while improving overall reliability.
The heavy-duty chassis occupies only 3U (5.25") of rack space while delivering up to2000 VA of clean, uninterruptible power. The rounded metal corners and rugged handles, aidin safe handling. Internally, all major components are well secured and electricallyinsulated to prevent damage due to shock and vibration. The optional heavy-duty rack slides provideeasy installation and removal of the unit with full extension. Rear shockisolation/alignment bushings off load the slides when the unit is fully engaged.
The internal shieldedinput transformer provides galvanic isolation with provisions for both domestic (115VAC, CONUS) and international (230 VAC, OCONUS) inputvoltages. The input voltage selection is automatic without having to open the UPS enclosure. Theunit also operates as a frequency converter, taking 46-70 hertz input andconverting it to 60 hertz power. Special EMI/RFI filters and inputpower factor correction minimize both input current and harmonics. The inputcircuit breaker and the galvanic isolation transformerall provide a double pole isolated source for all installations including shipboard systems oroverseas locations where phase references and grounding are not consistent.
The LED arrays keep the operator informed as tothe unit's status including load and battery levels. The high intensity audible alarm canbe heard in high noise environments.All controls and protective devices are brought to front and rear panels with criticalswitches having finger guards. Further, all front panel devices are recessed to preventdamage or accidental operation. The internal intelligent PDU allows control ofthe individual output circuits incorporating thermal and interlock interfacesfor additional control and safety, plus Battleshort override. The display andcontrol panel can be mounted remotely in the rack at eye level, or on the keyboard console,or on the unit front panel with only a logic level cable connection.
The rear panel provides lockingconnectors for the input and output power with various optional configurationsavailable. The output connectors are unique allowing the use of either standardNEMA 5-15P plugs or MS threaded metal shell connectors. The removable and washable intake air filters and high capacitystainless steel ballbearing fan provide added protection in both controlled and hostile environments. This reverse air flow version draws air through the front and exhausts out the rearvent into the rack. The batteries are maintenance free with immobilized electrolyte and areconstructed of flame retardant materials. For more information, see the BatteryTechnology section. The Status connectors provide both a contact andasynchronous serial interface with optional computersoftware providing loss of AC and low battery status as well as remote shut downcapability. The UPS Remote Control and the PDU Remote Control connectors provide aninterface to optional remote display/control panels. The PDUControl connector provides for ON/OFF control of loads using optional RemoteDistribution Units within the rack.
See the Power Distribution Units section for a listing ofstand alone PDUs. See the N3 Series
ETI0001-1237AA for aversion of this UPS without the integrated PDU and remote control.
Overall, the Rugged Power line is uniquely qualified for critical shipboard, vehicle,airborne or land based systems combining advanced modular design features with highlyreliable construction.
AC OUTPUT | |
Output voltage: UPS | 120 VAC true sinewave standard, others optional |
Output rating: UPS | 2000 VA standard in 3U chassis 0.65-0.75 pf standard, optional configurations to 24,000 VA |
Non-linear load capacity: UPS | Up to 100% non-linear load capability w/o derating |
Output voltage regulation: UPS | ± 3.0% static regulation of nominal ± 4.0% dynamic (0 to 50% load step) |
Overload surge capacity: UPS | 110% for 10 minutes; 125% for 30 seconds |
Harmonic distortion: UPS | Less than 5.0% into 100% non-linear load |
Output frequency: UPS | 60 Hz ± 1.0% independent of input frequency 50, 400 or 1000 Hz output available as an option |
Operational status | Status, load and battery LEDs, w/contacts RS-232 asynchronous serial status COM port Adjustable level,+90 dB audible alarm w/on/off |
AC INPUT | |
Input voltage selection: | Autoranging from nominal 115 VAC to 230 VAC |
Input voltage tolerance: UPS | 85-270 VAC @ full load without using battery, to 70 VAC @ 75% load |
Input frequency: | From 46 Hz to 70 Hz standard, optional to 440 Hz |
Input power factor: | Better than 99% typically |
Input/output isolation: | 2000 VA, up to 120 dB common mode, <1.0 mA leakage |
Input transient suppression: | Complies with IEEE 587 and UL 1449 |
Input control/protection: | Guarded 2 pole input breaker w/ UPS fuse Optional cold start to turn on w/o AC present |
Input power connection: | MS 3102A-22-2P, 3 pin, threaded locking |
INTERNAL BATTERY | |
Battery type: | Maintenance free immobilized electrolyte, Flame retardant materials (Oxygen Index 28+) |
Battery life: | Rated for continuous service life of 5 years |
DC protection: | Panel mounted fuse standard, breaker optional |
Battery time: | 15+ minutes @ 100% load, 30+ minutes @ 50% |
Battery recharge: | Recharged to nominal in <8 hours |
DISTRIBUTION PANEL | |
Output circuits: | Six controlled outputs via solidstate relays |
Output control: | Local/remote control panel w/rocker switches Thermal and remote interlock ON/OFF control |
Output receptacles: | MS / NEMA 5-15R threaded locking, various options |
MECHANICAL | |
Dimensions ( H x D x W ): | 5.25 (3U) x 28.0 x 19.0 in (133 x 711 x 483 mm) |
Rack Slide Mount Patterns: | Actron, Jonathan and General Devices slide patterns standard, others optional |
Rack rear alignment pins: | (2) shock isolation/alignment pin/socket sets |
Alternate Mounting Options: | Table, Wall, Floor, Portable, Horizontal/Vertical |
Unit weight: | 160 lb. (73 kg) with lift handles front |
Audible noise: | Less than 47 dB @ 5.0 ft., ANSI "A" scale |
Cooling type: | High capacity, negative pressure, forced air |
Cooling air direction: | Front intake, exhaust to rear, others optional |
Air intake filter: | Washable metal filter media, others optional |
ENVIRONMENTAL | |
Storage temperature: | -40° to 158° F ambient (-40° to 70° C) with fully charged batteries |
Operating temperature: | -4° to 131° F ambient ( -20° to 55° C), lower/ higher optional |
Operating humidity: | 0 to 95% relative humidity (non-condensing) |
Storage elevation: | Up to 40,000 ft (12,192 m) |
Operating elevation: | Up to 15,000 ft (4,572 m), higher optional |
STANDARDS | |
United States: | Meets UL-1778 standard for UPS equipment, MIL STDs 167-1, 454, 810, 901D Grade A, 1399-300A & 2000 |
Canada: | CSA C22.2 No. 107 UPS safety requirements |
EMI Protection: | EMI/RFI FCC Part 15, Class A; EN55022; MIL STD 461 |
OPTIONAL ACCESSORIES | |
Autoranging International Input, Cold Start, Alternate I/O Configurations, Dual Source Input, Battery Expansion, Batteryless Operation, Battery Charger/Conditioner, Power Distribution Units, Software Interface, 10BaseT Ethernet SNMP/HTTP port, Transport Cases, Slides and Mounting Kits |