LinkedIn



P/N: ETI0001-1252 Model: ETI0001-S3R-KIA/1.5, 1.5 kVA Rugged Rackmount Worldwide MilSpec UPS

Part Number:
ETI0001-1252
Model:
ETI0001-S3R-KIA/1.5 
TAC-4 P/N: S5444-00001
Rugged Mil Spec® 1550 VA 
Rackmount Global UPS


US Navy /Hewlett Packard / TAC-4, TAC-JW andTomahawk StandardProduct Military Power® S3 Configuration, IsolatedMil Spec UPS
1550 VA Rugged Rack Mount, Modular Power System
Accepts 85-270 VAC, 46-440 Hz Input or 22-32 VDC
Plus a Hot Swappable Battery Module

ETI0001-1252 Rugged MilSpec UPS Standard Front Panel Layout
ETI0001-1252 Rugged Mil Spec UPS Standard Front Panel Layout

ETI0001-1252 Rugged MilSpec UPS Standard Rear Panel Layout
ETI0001-1252 Rugged Mil Spec UPS Standard Rear Panel Layout

Front View of ETI0013-1101 Optional 1U Shallow Depth, Universal Mount PDU, ETI0013-1101 
Front View showing 2 CBs and 8 Outlets with Cord Restraints

Rear View of ETI0013-1101 Optional ETI0013-1101 Rear View showing provisions for 
4 Wall Mount Type Transformer Supplies with Tie Downs 

Top View of ETI0013-1101 Optional ETI0013-1101 Top View showing Shallow Depth

The field proven Military Power® UPS line is ideally suited for military,industrial, computer and telecommunications applications requiring high reliability, rugged construction, compact size and light weight design.These units are equally suited for use in shipboard, airborne, vehicular, fielddeployed or fixed locations with controlled or uncontrolled environments. The
ETI0001-1252 is specifically designed for lightweightglobal power deployment or equally well in shallow depth racks including TAC-4 racks and interfacing with  either the TAC-4 PDU or any of numerous ETIPDUs. 

The heavy-duty chassis occupies only 7" (4U) of rack space while delivering up to 1550 VA of clean, uninterruptible power. The rounded metal corners and rugged handles, aidin safe handling. Internally, all major components are well secured and electricallyinsulated to prevent damage due to shock and vibration. The optional heavy-duty rack slides provideeasy installation and removal of the unit with full extension.

The internal shieldedinput transformer provides galvanic isolation with provisions forboth domestic (115 VAC, CONUS) and international (230 VAC, OCONUS) inputvoltages. The autoranging input voltage selection allows inputting either 115 VAC or 230 VACwithout having to open the UPS enclosure. Special EMI/RFI filters and inputpower factor correction minimize both input current and harmonics. The inputswitch and the galvanic isolation transformer provide a double pole isolated source for all installations including shipboard systems oroverseas locations where phase references and grounding are not consistent. 

Alternately, theunit also accepts vehicular or aircraft power from nominal 24 VDC systems. The
ETI0001-1252 has the added benefit ofhaving a front drawout hot-swappable battery module. 

The LED arrays keep the operator informed as tothe unit's status including load and battery levels. The high intensity audible alarm canbe heard in high noise environments.All controls and protective devices are brought to front and rear panels with criticalswitches having finger guards. Further, all front panel devices are recessed to preventdamage or accidental operation. 

The rear panel provides lockingconnectors for the input and output power with various optional configurationsavailable. This reverse air flow version draws air through the front and exhausts out the rearvent into the rack. A removable and washable intake air filter and high capacitystainless steel ballbearing fan provide added protection in both controlled and hostile environments. The batteries are maintenance free with immobilized electrolyte and areconstructed of flame retardant materials. For more information, see the BatteryTechnology section. The twostatus D shell connectors provide both a contact and serial interface withoptional computer software providing loss of AC and low battery status as well as remote shut downcapability.

See the Power Distribution Units section for a listing ofstand alone PDUs. See the N5 Series
ETI0001-1482
for aversion of this UPS with an integrated PDU and remote control

Overall, the WorldPower line is uniquelyqualified for critical shipboard, vehicle, airborne or land based systems combiningadvanced modular design features with highly reliable construction.

Technical Specifications:
P/N:
ETI0001-1252
AC OUTPUT
Output voltage: 120 VAC true sinewave std, up to 600 VAC optional
Output rating: UPS 1550 VA,  standard in 4U x 19" chassis
0.65-0.75 pf std, optional configurations to 24,000 VA
Non-linear load capacity: Up to 100% non-linear load capability w/o derating
Output voltage regulation: UPS ± 3.0% static regulation of nominal
± 4.0% dynamic (0 to 50% load step)
Overload surge capacity: 110% for 10 minutes; 125% for 30 seconds
Harmonic distortion: Less than 5.0% into 100% non-linear load
Output frequency: UPS 60 Hz ± 1.0% independent of input frequency
50, 400 or 1000 Hz output available as an option
Operational status Status, load and battery (16) LEDs, w/contacts
RS-232 asynchronous serial status COM port
Adjustable level,+90 dB audible alarm w/on/off
AC INPUT
Input voltage selection: Autoranging from nominal 115 VAC to 230 VAC
Input voltage tolerance: UPS +15% -25%, or 85-135 and 170-270
Input frequency: From 46 Hz to 440 Hz
Input/output isolation: 2000 VA,
120 dB common mode, <1.0 mA leakage
Input transient suppression: Complies with IEEE 587 and UL 1449
Input control/protection: Guarded 2 pole switch (S3) w/fuse (F2)
Input power connection: MS 3102A-22-2P, 3 pin, locking
DC INPUT / INTERNAL BATTERY
External DC input: Nominal 22 to 32 VDC
External DC protection: Rear panel mounted fuse (F3)
External DC connector: MS 3102A-24-9P, 2 pin, locking
Internal battery type: Maintenance free immobilized electrolyte,
Flame retardant materials (Oxygen Index 28+)
Internal battery life: Rated for continuous service life of 5 years
Internal DC protection: Front panel mounted fuse (F1)
Internal battery time: 10+ minutes @ 1000 watt load, 20+ minutes @ 50%
Internal battery recharge: Recharged to nominal in <8 hours
Internal battery replacement: Drawout/plug-in module from front of unit
DISTRIBUTION PANEL
Output circuits: One output standard, optional configurations
Output control: Guarded 3 pole switch (S5)
Output receptacles: MS 3102A-22-2S, 3 pin locking, other options
MECHANICAL
Dimensions ( H x D x W ): 7.00 (4U) x 20.9 x 19.0 in (178 x 531 x 483 mm)
Rack Slide Mount Patterns: Actron slide pattern, others optional
Rack rear alignment pins: (2) shock isolation/alignment pin/socket sets
Alternate Mounting Options: Table, Wall, Floor, Portable, Horizontal/Vertical
Unit weight: 99 lb. (45 kg) with lift handles front and rear
Audible noise: Less than 47 dB @ 5.0 ft., ANSI "A" scale
Cooling type: High capacity, negative pressure, forced air
Cooling air direction: Front intake, exhaust to rear
Air intake filter: Washable metal filter media, others optional
ENVIRONMENTAL
Storage temperature: -13° to 140° F ambient (-25° to 60° C)
Operating temperature: 50° to 104° F ambient ( 10° to 40° C)
Operating humidity: 0 to 95% relative humidity (non-condensing)
Storage elevation: Up to 40,000 ft (12,192 m)
Operating elevation: Up to 15,000 ft (4,572 m), higher optionally
STANDARDS
United States: Meets UL-1778 standard for UPS equipment,
MIL STDs 810, 454 & 1399 Shock/Vib/Electrical
Canada: CSA C22.2 No. 107 UPS safety requirements
EMI Protection: EMI/RFI FCC, Class A; EN55022; MIL STD 461
OPTIONAL ACCESSORIES
  Alternate I/O Configurations, Dual Source Input, Cold Start, Battery Expansion, Transport Cases

Request Product Information
*(denotes required field)
Contact ETI by mail at:
Energy Technologies, Inc.
219 Park Avenue East
Mansfield, OH 44902-1845
USA

Contact ETI by phone or fax:
Voice: 419-522-4444